By Leon Harris
Published in INsite
With
the increasing use of contract security guards and patrols by the
aged care sector, both client and security provider must be clear
of mutual obligations, expectations and limitations of these services.
With so many legislative and other requirements placed on aged
care operators it is understandable that some important Australian
Standards sometimes fail to get an airing in compliance programs. Australian
Standards in their various areas assist organisations to develop
benchmarks, to establish expectations between stakeholders (e.g.
facility and security company) and are sometimes used in evidence
as part of civil litigation. One Standard worth considering
is the Australian Standard on Guards and Patrols AS 4421: 1996,
and Amendment B 1999 Minimum Alarm Response Times.
From our experience in undertaking security reviews of aged care
facilities it has been identified that there is often uncertainty
by operators as to what standard of service they should expect
from their security providers. For example, what should be
the Monitoring Response time? This is the response by the
alarm monitoring company (control station) to advise the security
patrol company (or designated person, e.g. key holders) they have
received an alarm. Or, what should be the Patrol Response time? This
is the time in which the patrol company responds to a call after
being notified by the monitoring control room (often a separate
company) of receiving an alarm.
Part B3 of the amendment for Monitoring Response Time states: “The
following monitoring response time shall apply:
| (a) |
When patrol response is the
first action |
Less than or equal
to 5 min. |
| (b) |
When patrol response is a subsequent
action from the time authority is given or confirmed to send
a patrol response. |
Less than or equal to 5 min. |
| (c) |
When late to close |
Less than or equal to 25 min.” |
Part B4.1 of the Amendment for Patrol Response Time states: “…the
following patrol response times shall apply:
(a) |
Standard alarm response |
Less than or
equal to 35 min. |
(b) |
Late-to–close |
Less than or
equal to 45 min. |
(c) |
Weekday response, where provided |
Less than or
equal to 75 min.” |
In both B3 and B4.1 response times may be negotiated, however,
these should be agreed upon and articulated in the Service Level
Agreement (SLA).
Response times in both scenarios should be checked on a regular
basis. This can be undertaken by requesting a report from the monitoring
station which will provide the time of receipt of an alarm to notifying
the security patrol company and/or authorised key holders (those
people in the organisation given the security responsibility) and
possibly (depending on arrangements) the arrival on site of the
security patrol response.
A definition of particular interest is the Total Response Time
(TRT), this is the time elapsed between an alarm activation (A)
and arrival on site of a security response (AOS). The TRT
does not include the alarm reset time (ART).
It should be noted there may be genuine exceptional circumstances
for delays in response times, e.g. storms, floods, road accidents,
etc.
There are other exemptions under Section B4.2 of which a user
of these services should also be aware.
- “Where the client is responsible for late response time,
such as where the patrol officer is instructed to meet the client’s
representative on site at a prearranged time, or the patrol officer
is unable to gain access due to keys being changed.
- Where external checks are carried out by another patrol officer
or inspector within the relevant patrol response time.
- NOTE: Such a situation may occur when the patrol vehicle with
the keys is delayed.
- In non-response areas and country areas.
NOTE: The response area should be agreed between the client an the
monitoring company.”